Type T205B
5
Figure 4. Balanced Trim Assembly
!
WARNING
A regulator may vent some gas to
the atmosphere. In hazardous or
ammable gas service, vented gas may
accumulate and cause personal injury,
death or property damage due to re or
explosion. Vent a regulator in hazardous
gas service to a remote, safe location
away from air intakes or any hazardous
area. The vent line or stack opening
must be protected against condensation
or clogging.
3. To keep the vent assembly (key 26, Figure 6) from
being plugged or the spring case (key 3) from
collecting moisture, corrosive chemicals or other
foreign material, point the vent down or otherwise
protect it. The diaphragm casing (key 4) may be
rotated in order to obtain desired positioning.
4. To remotely vent the regulator, remove the vent
(key 26, Figure 6) and install obstruction-free
tubing or piping into the 1/4 NPT vent tapping.
Provide protection on a remote vent by installing
a screened vent cap into the remote end of the
vent pipe.
5. The Type T205B requires a downstream control
line. Be sure to install the control line before
putting the regulator into operation. Make the
control line as short and straight as possible
and do not install it in a location where ow may
be turbulent. Restrictions in the control line can
prevent proper pressure registration. When using
a hand valve, it should be a full ow valve, such
as a full port ball valve. Install the control line
sloping downward toward the tank to prevent
condensation buildup and avoid low points (or
traps) that could catch liquid. The sensing line
must enter the tank above the liquid level at a
point that senses the vapor space pressure and is
free from turbulence associated with tank nozzles
or vents. The control line pipe should be at least
1/2-inch / 13 mm in diameter and increase 1 pipe
size for every 10 feet / 3.05 m of control line, with
setpoints less than 5-inches w.c. / 12 mbar.
6. An upstream shutoff valve is recommended
to simplify maintenance to the regulator. It is
advisable to install a pressure gauge between the
upstream shutoff valve and the blanketing valve.
BIAS SPRING SEAT (KEY 40)
BIAS SPRING (KEY 39)
GUIDE INSERT (KEY 18)
DISK (KEY 13)
STEM (KEY 14)
INSERT SEAL O-RING (KEY 12)
Comentarios a estos manuales