Type T205B
4
Figure 3. Type T205BActuator Casing Drainage 
Installation
!
WARNING
Personal injury, property damage,
equipment damage or leakage due to
escaping gas or bursting of pressure-
containing parts may result if this regulator
is overpressured or installed where
service conditions could exceed the limits
given in the Specications section or
where conditions exceed any ratings of
the adjacent piping or piping connections.
Refer to Overpressure Protection section
for recommendations on how to prevent
service conditions from exceeding
those limits.
To avoid such injury or damage,
provide pressure-relieving or pressure-
limiting devices (as required by
the appropriate code, regulation or
standard) to prevent service conditions
from exceeding limits.
Additionally, physical damage to the
regulator could cause personal injury or
property damage due to escaping gas.
To avoid such injury or damage, install
the regulator in a safe location.
Note
If the regulator is shipped mounted on
another unit, install that unit according
to the appropriate instruction manual.
1. Only personnel qualied through training and
experience shall install, operate and maintain
a regulator. For a regulator that is shipped
separately, make sure there is no damage to or
debris in the regulator. Also ensure that all tubing
and piping are clean and unobstructed.
2. The regulator may be installed in any position
as long as the ow through the body is in the
direction indicated by the arrow on the body.
For proper operation to achieve the published
capacities at low setpoint, the spring case barrel
should be installed pointing downward as shown
in Figure 1. For complete actuator drainage, the
regulator should be installed as shown in Figure 3.
If continuous operation of the system is required
during inspection or maintenance, install a
three-valve bypass around the regulator.
HORIZONTAL PIPELINE
VENT POINTED DOWN
DOWNSTREAM CONTROL LINE
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE