NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[125 of 149]
CONFIG B_
On Delay Time:
Type the required alarm on delay time period* and a modifier*, then
press
ENTER
. The on delay time is the amount of seconds that an alarm
condition must exist before the system recognizes it as an alarm
condition.
* Enter a valid value (0-9999) then the modifier (s for seconds, m for
minutes, h for hours). If no modifier entered, modifier defaults to
seconds.
Note:
The timing involved in the operation of the rectifier sequencing
feature will be affected if the alarm delay attributes for the binary
channels selected to control the sequencer are configured.
Configuring the "On Delay" or "Off Delay" for the AC Fail / Transfer
input or Standby On / Proper Operate input will postpone
detection (signals may have already been detected by the
transfer device) of an AC Failure or Proper Operate signal by the
rectifier sequencing software.
Save changes (Y or N):
Type
Y
if the above entered data is to be saved in the current binary
configuration file and
N
if not, then press
ENTER
.