OS2 NACE
4
Packing gland
Description Valve
OSB VSE Standard
Assembly 181 089 181 090 181 104
Packing gland and stem 181 040 181 040
Packing gland 144 126
O-ring 400 514 400 505 400 514
O-ring 400 221
Fastening screw H M7 402 028 402 028
Fastening screw H M8 402 036 402 036
Flat washer (7) 405 005 405 005
Flat washer (8) 405 006 405 006
4
DESCRIPTION AND SPARE PARTS
(BM)
6c - Standard packing
gland
6d - VSE packing gland
ø24
ø 7
Packing gland assembly
Items in bold are spare parts
OPERATION (BM)
The detection stage consists of two parts:
• the releasing stem (1),
• the 1
st
stage trigger (2).
Through the intermediate of the safety manometric box (BMS), the
pressure provokes a pin movement (D1 or D2), which provokes the
rotation of the releasing stem (1) and frees the 1
st
stage trigger (2).
The power stage consists of two parts:
• the 2
nd
stage trigger (3),
• the cam (4).
The 2
nd
stage trigger (3), activated by the 1
st
stage trigger (2),
frees the cam (4), which provokes the valve to close.
After release, the resetting is ensured in two stages:
(detection stage, then power stage) see "commissioning".
Position indicator
The position of the detection stage can be seen through the
position indicator glass.
Memorization
The releasing stem will only start moving when pressure ap-
proaches the pressure set point. In all other cases, it remains
fixed. Furthermore the assembly has a very high resistance to
shocks. If pressure approaches the set point, the releasing stem
turns, but with the slightest shock or vibration it will go back to it’s
initial position and pressure returns to normal. The mechanism is
said to be non memorizing.
Resistance to shocks
This assembly has a remarkable resistance to shocks (20 vertical
shocks of 4 J and 20 pendular shocks of 9.81 J), with pressure close
to set point (for example: 186 mbar for a set point of 200 mbar).
CONNECTIONS (BM)
• Fixation BM / Connector:
H M7 or H M8 screws
16 N.m torque
• Sealed BM / Connector:
Flat O-ring (water resistant)
Packing gland (gas resistant)
• Mechanism contact / Slam shut valve:
Control rod
• BM connector / atmosphere:
Integrated vent nipple with screen (supplied) or compression
fitting (supplied) for 8/10 tube (not supplied)*
• Electrical connection:
See page 6
* The 8/10 tube should be angle-shaped on the top to avoid water from
entering.
7 - Mechanism
TRAVEL STOP
D1
D2
2
3
4
VALVE
1
N09
N07
N08
Europe, Middle East, and Africa Document Only