Type OS2
11
Releasing by Max. and Min. (Diaphragms
or Bellows Only)
• Adjusting the releasing screw
Free the min. hook (key 2).
Then in the following conditions:
- setpoint spring decompressed (adjustment screw
(key 5) unscrewed),
- pressure equal to the max. releasing pressure required
in the BMS,
adjust the releasing screw (key 1) to X = 0 mm (detection
stage set).
Release manually.
Unscrew the releasing screw (key 1) 2 turns, which
represents a distance of approximately 1.5 mm.
Jam nut (key 3).
• Max. adjustment
Same procedure as paragraph “Adjusting max. only
releasing pressure”
• Min. adjustment
Admit an average pressure between max. and min.,
(for example: regulator set-point pressure).
Set the slam shut.
Admit a pressure equal to the min. Pd min. releasing
pressure required.
Adjust the hook (key 2) by progressively moving nuts
(key 6) and (key 7) until it releases.
Jam nuts (key 6) and (key 7).
Check the pressure value at the releasing point (adjust
if necessary).
Type BMS 2 with 1 Max. Only Type BMS 1
Releasing by Max. Only
• Adjusting the max. push button
Remove the hook (key 2).
Then in the following conditions:
- no pressure in the BMS,
- setpoint spring compressed so that the distance
between the push button (key 1) and the pin D2 no
longer increases,
Adjust the push button (key 1) to X = 1.5 mm (detection
stage set).
Jam nut (key 3).
N23
1
X
Y
D2
D1
35
6
2
4
MAX. ONLY TYPE BMS1
ADJUSTMENT
• Adjusting the max. only releasing pressure
Same procedure as paragraph “Adjusting the max. only
releasing pressure”.
Releasing by Min. Only
• Adjusting the min. only releasing pressure
Remove the max. push button (key 1) or screw it tight to
neutralize it.
Jam nut (key 3).
Then in the following conditions:
- setpoint spring decompressed (adjustment screw
(key 5) unscrewed),
- pressure equal to releasing pressure required in the
BMS, adjust the min. hook (key 2) to Y = 1.5 mm
(detection stage set).
Jam nut (key 6).
• Adjusting the min. only releasing pressure
Same procedure as paragraph “Adjusting max. only
releasing pressure”.
Releasing by Max. and Min.
• Adjusting the push button
The min. hook (key 2) is completely unscrewed.
Then in the following conditions:
- setpoint spring decompressed (adjustment screw
(key 5) unscrewed),
- pressure equal to the max. releasing pressure required
in the BMS.
adjust the push button (key 1) to X = 0 mm
(detection stage set).
Release manually.
Unscrew the push button (key 1) 2 turns, which represents
a distance of approximately 1.5 mm.
Jam nut (key 3).
• Adjusting the releasing pressure to max. and min.
Max. adjustment
Same procedure as paragraph “Adjusting the max. only
releasing pressure”.
Min. adjustment
Admit an average pressure between max. and min.,
(for example regulator set-point pressure).
Set the detection stage.
Admit a pressure equal to the min. releasing
pressure required.
Screw the hook (key 2) progressively until detection
stage release.
Jam nut (key 6).
Check the pressure value at the releasing point
(adjust if necessary).