CSB400 Series
6
Table 8. Regulator and Slam-shut OPSO and UPSO Pressure Ranges
Example: If a non-standard setpoint is needed, see the following example for the proper use of Table 8.
Non-standard setpoint = 140 mbar / 2 psig, using the value presented above, the factory set of the token relief will be
1.3 x 140 = 182 mbar / 2.6 psig. The factory OPSO and UPSO set pressures are 165% and 50% of the non-standard
setpoint, respectively. The resulting settings are: OPSO = 231 mbar / 3.4 psig and UPSO = 70 mbar / 1 psig.
TYPE
REGULATOR SLAM-SHUT MODULE
Set Pressure
Range
Standard
Setpoints
Token Relief
Set
(1)(2)
Available
Token Relief
Range Shown
as a % of
Regulator
Setpoint
Overpressure Shutoff (OPSO) Underpressure Shutoff (UPSO)
Minimum
Required
Difference
between Token
Relief and
OPSO Set
Standard
OPSO Set
Values
(1)
P
dso
OPSO Set
Range as a %
of Regulator
Setpoint
Standard
UPSO Set
Values
(1)
P
dsu
UPSO Set
Range as a %
of Regulator
Setpoint
mbar psig mbar psig mbar psig Min
(2)
Max mbar psig mbar psig Min Max mbar psig Min Max
CSB404,
CSB404F
and
CSB414
17 to
24
0.25 to
0.35
20 0.29 34 0.49
170% 215% 8 0.12
43 0.62
215% 270%
10 0.15
50% 56%
21 0.30 36 0.52 45 0.65 11 0.16
24 to
35
0.35 to
0.51
27 0.39 41 0.59
150% 160% 10 0.14
51 0.74
190% 200%
14 0.20
50% 60%
30 0.44 45 0.65 57 0.83 15 0.22
35 0.50 53 0.76 67 0.96 18 0.26
35 to
60
0.51 to
0.87
50 0.70 70 1.0
140% 158% 16 0.23
90 1.3
180% 200%
25 0.36
50% 70%
60 0.87 84 1.2 108 1.57 30 0.44
54 to
100
0.8 to
1.5
75 1.10 98 1.4
130% 140% 20 0.29
128 1.85
170% 190%
38 0.54
50% 70%
100 1.5 130 1.9 170 2.47 50 0.73
CSB424,
CSB424F
and
CSB434
100 to
160
1.5 to
2.3
150 2.2 195 2.8
130% 140% 40 0.58
248 3.59
165% 175%
75 1.1
50% 70%
160 2.3 208 3.0 264 3.83 80 1.2
138 to
300
2.0 to
4.4
300 4.4 375 5.4 125% 140% 50 0.73 450 6.53 150% 165% 150 2.2 50% 70%
276 to
517
4.0 to
7.5
500 7.3 625 9.1 125% 140% 60 0.87 700 10.2 140% 180% 250 3.6 50% 70%
CSB454
(3)
500 to
1000
7.3 to
14.5
1000 14.5 - - - - - - - - - - - - - - - - - - - - - - - - 1320 19.2 112% 140% 500 7.3 50% 70%
1000 to
3000
14.5 to
43.5
1200 17.4 - - - - - - - - - - - - - - - - - - - - - - - - 1600 23.2 112% 133% 600 8.7
50% 70%
1500 21.6 - - - - - - - - - - - - - - - - - - - - - - - - 1900 27.6 112% 127% 750 10.9
2000 29.0 - - - - - - - - - - - - - - - - - - - - - - - - 2400 34.8 112% 120% 1000 14.5
3000 43.5 - - - - - - - - - - - - - - - - - - - - - - - - 3400 49.3 112% 113% 1500 21.8
1. Standard factory set shown. Factory set is at the Minimum value of the range indicated. Range indicated is a percentage of Setpoint. Percentage indicated is based on the Set Pressure Range
in which that setpoint resides. If non-standard sets are required, adherence must be made to constraints shown in Table 7, including Token Relief Set Range, OPSO and UPSO set range and
Minimum Required difference between Token Relief and OPSO Set.
2. Minimum Token Relief values apply to -20 to 60°C / -4 to 140°F service temperatures. For service below -20°C / -4°F, add 8 mbar / 0.12 psig to the minimum Token Relief value listed.
3. Token Relief is not available for the Type CSB454.
Comentarios a estos manuales