Emerson CSB400 Manual de instrucciones Pagina 16

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 15
CSB400 Series
16
The range of allowable pressure settings
for the primary regulator is stamped on
the nameplate. If the required setting
is not within this range, substitute the
correct spring (as shown in Table 6). If the
spring is changed, re-stamp the nameplate
to indicate the new pressure range.
A pressure gauge must always be used
to monitor downstream pressure while
adjustments are being made.
For Types CSB400 and CSB420
1. Remove the closing cap (key 60, Figure 16).
2. To increase the outlet setting, turn the adjusting
screw (key 65) clockwise. To decrease the outlet
setting, turn the adjusting screw counterclockwise.
3. Replace the closing cap.
For Type CSB450
1. Loosen the hex nut (key 58, Figure 16).
2. To increase the outlet setting, turn the adjusting screw
(key 65, Figure 16) clockwise. To decrease the outlet
setting, turn the adjusting screw counterclockwise.
3. Tighten the hex nut.
CSB400 Series with Integral True-Monitor™
When adjusting the primary regulator and Integral
True-Monitor for operation, ensure that the pressure
differences between the primary regulator and the
integral monitor shown in Table 7 are observed. For
example, if the primary regulator setpoint is set at
20 mbar / 8 inches w.c., then the Integral True-Monitor
should be set at a minimum of 35 mbar / 14 inches w.c.
or higher.
To test the Integral True-Monitor operation, the primary
regulator setpoint must be adjusted above the Integral
True-Monitor’s setpoint to simulate a failure of the
primary regulator. If the spring range of the primary
regulator is sufciently high, it can simply be adjusted
above the Integral True-Monitor’s setpoint by following
step 2 above. Otherwise, a different spring with a
setpoint higher than the Integral True-Monitor’s setpoint
must be installed to check the operation of the
Integral True-Monitor.
CSB400 Series with Slam shut
When adjusting the primary regulator and slam shut for
operation, refer to Table 8 for the OPSO setpoints and
also the combined OPSO and UPSO setpoints of the
slam shut for a given regulator spring ranges.
CAUTION
Equipment installed downstream the
Type VSX slam shut device can be
damaged if the following procedure for
resetting the Type VSX slam shut device
is not followed. This equipment
includes the integral Type VSX or
regulator configurations.
Step 1:
To properly reset the Type VSX slam shut after it
has been tripped to the closed position, a at-head
screwdriver must be inserted into the position shown
in Figure 8 on the backside of the reset button (refer
to Type VSX4 Instruction Manual, key 30, Figure 8).
Step 2:
The screwdriver should be slowly rotated to gradually
pull the reset button (refer to Type VSX4 Instruction
Manual, key 30) away from the Type VSX device. This
slow movement allows for a slow bleed of the pressure
across the Type VSX slam shut’s disk and seat area.
The operator should be able to hear the pressure
bleeding through the system.
Step 3:
When the pressure has equalized and the air
bleeding sound has dissipated, the reset button (refer
to Type VSX4 Instruction Manual, key 30) should be
pulled completely away from the Type VSX slam shut
device by hand until the internal shut-off mechanism
has been re-latched.
Step 4:
Once the operator feels the click of the re-latch
occurring, the reset button (refer to Type VSX4
Instruction Manual, key 30) should be pushed
completely back into its original position.