CS800 Series
16
3. Inlet pressure should be released automatically
downstream as the regulator opens in response to the
lowered pressure on the diaphragm.
4. Close outlet shut-off valve.
Maintenance and Inspection
WARNING
!
To avoid personal injury or equipment
damage, do not attempt any maintenance
or disassembly without rst isolating
the regulator from system pressure and
relieving all internal pressure as described
in “Shutdown” section.
Test the regulator that has been
disassembled for repair to ensure
that it is operating properly before
being returned to service. Only parts
manufactured by Emerson™ should be used
for repairing Fisher
®
regulators. Restart gas
utilization equipment according to normal
Startup procedures.
Due to normal wear or damage that may
occur from external sources, inspect and
maintain this regulator periodically. The
frequency of inspection and replacement of
parts depends upon the severity of service
conditions or the requirement of local, state
and federal rules and regulations.
Perform periodic inspection on Wide-Open
Monitor regulators, Integral True-Monitor™ or
Slam-shut overpressure protection modules
to ensure protection of the downstream
system in the event of a failure to the primary
regulator. This inspection must test that the
wide open monitor, Integral True-Monitor or
Slam-shut functions as intended.
Maintenance on CS800 Series with
Secondary Seat™ Protection
Types CS805 and CS825 regulators do not have any means
to alert when the Secondary Seat operates at lockup. A lock-up
test can be done on the regulator to determine if the lock-up
pressure has elevated to or near the values in Table 7, under the
heading Types CS805 and CS825. If so, replace the regulator
primary disk and orice.
Internal relief operation on units equipped with Secondary Seat
Protection is an indication that the Secondary Seat Protection on
the Types CS805IR and CS805IQ may not be working and that
the Types CS806IR and CS806IQ Secondary Seat may have
closed. Maintenance should address any potential causes for
internal relief operation as well as other regulator malfunctions
separate from the Secondary Seat.
CAUTION
When applying pressure to the regulator
spring case through the vent, care must
be taken not to exceed 3 psig / 0.21 bar,
which is the maximum differential across
the diaphragm.
Types CS804, CS824 and CS854 with
Slam-shut Module
When adjusting the Primary Regulator and Slam-shut for
operation, reference Tables 10 and 11 and the footnotes in
each table for the OPSO and OPSO/UPSO setpoints of the
slam-shut for the given regulator spring ranges.
CAUTION
Equipment installed downstream the
Type VSX8 slam shut device can be damaged
if the following procedure for resetting the
Type VSX8 slam shut device is not followed.
This equipment includes the integral
Type VSX8 or regulator congurations.
1. To properly reset the Type VSX8 Slam-shut after it has
been tripped to the closed position, insert a at-head
screwdriver into the position shown in Figure 8 on
the backside of the reset button (refer to Type VSX8
Instruction Manual, key 30, Figure 8).
2. Slowly rotate the screwdriver to gradually pull the reset
button (refer to Type VSX8 Instruction Manual, key 30)
away from the Type VSX8 device. This slow movement
allows for a slow bleed of the pressure across the
Type VSX8 Slam-shut’s disk and seat area. The operator
should be able to hear the pressure bleeding through
the system.
3. When the pressure has equalized and the air bleeding
sound has dissipated, completely pull the reset button
(refer to Type VSX8 Instruction Manual, key 30) away
from the Type VSX8 Slam-shut device by hand until the
internal shut-off mechanism has been re-latched.
4. Once the operator feels the click of the re-latch occurring,
completely push the reset button (refer to Type VSX8
Instruction Manual, key 30) back into its original position.
Shutdown
Installation arrangements may vary, but in any installation
it is important that the valves be opened or closed slowly
and that the outlet pressure be vented before venting
inlet pressure to prevent damage caused by reverse
pressurization of the regulator. The steps below apply to the
typical installation as indicated.
1. Open valves downstream of the regulator.
2. Slowly close the upstream shut-off valve.