Instruction Manual
D103176X012
Introduction and Specifications
April 2014
7
Table 1‐2. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level Performance Criteria
(1)
Enclosure
Electrostatic discharge
(ESD)
IEC 61000-4-2
6 kV contact
8 kV air
B
Radiated EM field IEC 61000-4-3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field
IEC 61000-4-8 30 A/m at 50 Hz, 60 sec A
I/O signal/control
Burst (fast transients) IEC 61000-4-4
$1 kV
A
Surge IEC 61000-4-5
$1 kV (line to ground only, each)
B
Conducted RF IEC 61000-4-6 150 kHz to 80 MHz at 10 Vrms A
Performance criteria is + / - 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Related Documents
Other documents containing information related to the DVC2000 digital valve controller include:
D Fisher FIELDVUE DVC2000 Digital Valve Controller Quick Start Guide (D103203X012)
D Bulletin 62.1:DVC2000—Fisher FIELDVUE DVC2000 Digital Valve Controller (D103167X012)
D INMETRO Hazardous Area Approvals for FIELDVUE DVC2000 Digital Valve Controller (D103780X012)
D FIELDVUE Digital Valve Controller Split Ranging - Supplement to HART Communicating Fisher FIELDVUE Digital
Valve Controller Instruction Manuals (D103262X012)
D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM) - Supplement to HART
Communicating Fisher FIELDVUE Instrument Instruction Manuals (D103263X012)
D Audio Monitor for HART Communications - Supplement to HART Communicating Fisher FIELDVUE Instrument
Instruction Manuals (D103265X012)
D HART Field Device Specification - Fisher FIELDVUE DVC2000 Digital Valve Controller (D103783X012)
D Using the HART Tri-Loopt HART-to-Analog Signal Converter with Fisher FIELDVUE Digital Valve Controllers -
Supplement to HART Communicating Fisher FIELDVUE Digital Valve Controller Instruction Manuals (D103267X012)
These documents are available from your Emerson Process Management sales office. Also visit our website at
www.FIELDVUE.com.
Vista de pagina 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 107 108

Comentarios a estos manuales

Sin comentarios