BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 252
Table 82 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
, Liebert PDX
- Analog Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance Object Name Access Notes
Extra
Notes
Air
Air Temperature Set Point Analog_Value 1 5008_1 RW Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Air Temperature Set Point Analog_Value 10001 5008_1_deg_F RW Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Air Temperature Proportional
Band
Analog_Value 2 5325_1 RW Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Air Temperature Proportional
Band
Analog_Value 10002 5325_1_deg_F RW Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Air Temperature Dead Band Analog_Value 3 5011_1 RW Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Air Temperature Dead Band Analog_Value 10003 5011_1_deg_F RW Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Air Temperature Control
Integration Time
Analog_Value 4 5326_1 RW Units: min
1, 2, 3, 4,
5, 6, 7, 8, 9
Today's High Air Temperature Analog_Value 5 5327_1 RD Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Today's High Air Temperature Analog_Value 10005 5327_1_deg_F RD Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Today's High Air Temperature
Time
Analog_Value 6 5328_1 RD
Units: Seconds
since Midnight
1, 2, 3, 4,
5, 6, 7, 8, 9
Today's Low Air Temperature Analog_Value 7 5329_1 RD Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Today's Low Air Temperature Analog_Value 10007 5329_1_deg_F RD Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Today's Low Air Temperature
Time
Analog_Value 8 5330_1 RD
Units: Seconds
since Midnight
1, 2, 3, 4,
5, 6, 7, 8, 9
Air - Supply Air
Supply Air Temperature Analog_Value 19 5002_1_1 RD Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Supply Air Temperature Analog_Value 10019 5002_1_1_deg_F RD Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Supply Air Temperature Set
Point
Analog_Value 20 5331_1_1 RW Units: deg C 1
Supply Air Temperature Set
Point
Analog_Value 10020 5331_1_1_deg_F RW Units: deg F 1
Supply Air Over Temp
Threshold
Analog_Value 21 5014_1_1 RW Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Supply Air Over Temp
Threshold
Analog_Value 10021 5014_1_1_deg_F RW Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Supply Air Under Temp
Threshold
Analog_Value 22 5018_1_1 RW Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Supply Air Under Temp
Threshold
Analog_Value 10022 5018_1_1_deg_F RW Units: deg F
2, 3, 4, 5,
6, 7, 8, 9