Emerson Liebert IntelliSlot Unity Communications Interface Card Manual de servicio Pagina 112

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 400
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 111
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 106
Alarm Points
Discrete alarm objects available;
use auto-discover for this unit
Communications 40289 1 Bit 0
Output Undervoltage 40289 1 Bit 1
Output Overvoltage 40289 1 Bit 2
Output Overcurrent 40289 1 Bit 3
Frequency Deviation 40289 1 Bit 4
Ground Overcurrent 40289 1 Bit 5
Transformer Overtemp 40289 1 Bit 6
Ground Fault 40289 1 Bit 7
Ground Failure 40289 1 Bit 8
Liquid Detected 40289 1 Bit 9
Security Alarm 40289 1 Bit 10
Phase Rotation/Loss 40290 1 Bit 0
Datawave Overtemperature 40290 1 Bit 1
Emergency Shutdown 40290 1 Bit 2
Load On Bypass 40290 1 Bit 3
Local Alarm #1 40290 1 Bit 4
Local Alarm #2 40290 1 Bit 5
Output Voltage THD 40290 1 Bit 6
Custom Alarm #1 40290 1 Bit 7
Custom Alarm #2 40290 1 Bit 8
Setpoints (View)
None 1
Control Points (Set)
None 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 33 Liebert FPC
, Liebert PPC
- Input and Holding (continued)
Controller Power Monitoring Panel - PMP2
Liebert Products
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units