MODBUS Termination Blocks Standard Values • 27
i1P Free of voltage digital input polarity CLOP CL Pr2
d1d Digital input 1 (free of voltage) activation de-
lay
0 to 255 min 0 Pr2
i2P Main voltage digital input polarity CLOP CL Pr2
i2F Main voltage digital input function CCL, rL CCL Pr2
d2d Digital input 2 (Main voltage) activation delay 0 to 255 min 0 Pr2
ALARMS
dAo Alarm delay after restarting regulation 0.0 to 42.0 min: tens of seconds 10.0 Pr2
tdA Type of alarm signaled by relay ALL, SH, PrE, di ALL Pr2
LPL Lower pressure limit for superheat regulation
(related to PrM parameter)
PA4 to P20 bar/ PSI -0.5 Pr2
MOP Maximum operating pressure threshold
(related to PrM parameter)
PA4 to P20 bar/ PSI 11.0 Pr2
LOP Minimum suction pressure limit
(related to PrM parameter)
PA4 to P20 bar/ PSI -0.5 Pr2
PHY Pressure alarm hysteresis 0.1 to 5.0 bar/ 1to 72 PSI 0.1 Pr2
dML delta MOP-LOP 0 to 100% 30 Pr2
MSH Maximum superheat alarm LSH to 32.0 °C/ LSH to 176 °F 80.0 Pr1
LSH Lowest superheat alarm 0.0 to MSH°C/ 32 to MSH°F 2.5 Pr1
SHy Superheat hysteresis 0.1 to 25.5°C/ 1 to 77°F 0.1 Pr2
SHd Superheat alarm activation delay 0 to 255 sec 120 Pr1
FrC Fast-recovery constant 0 to 100 sec 50 Pr2
DISPLAY
Lod Local display SH - PErP1 - P2 SH Pr1
CF Temperature measurement units °C - °F °C Pr2
PMU Pressure measurement unit bArPSI bAr Pr2
rES Resolution (only °C) dEin dE Pr2
PrM Type of pressure (absolute/ relative) rELAbS rEL Pr2
CLP Cooling call percentage Read only --- Pr2
tP1 Temperature probe value Read only --- Pr1
PPr Pressure probe value Read only --- Pr1
tP2 Temperature converted from pressure probe Read only --- Pr1
OPP Actual opening percentage Read only --- Pr1
d1S Free of voltage digital input state Read only --- Pr1
d2S Main voltage digital input state Read only --- Pr1
Adr Serial address 1 to 247 1 Pr2
Mod MODBUS type StDAdU StD Pr2
Ptb Parameters map --- --- Pr2
rEL Release software --- --- Pr2
Pr2 Second level menu --- --- Pr1
Label Description Range Default Level
Table 20-1 - XEV22D Standard Parameter Values