6 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
6 Valve Connections and Configuration
If you can locate your valve in the table, select the valve through the tEP parameter. This way, you can be
sure of the correct configuration (refer to Table 6-1).
Regarding connections, use Table 6-2 below for a quick reference on the connection mode for valves of dif-
ferent manufacturers. In any case, the unique and valid reference has to be considered the datasheet made by
manufacturer of the valve:
CAUTION! To avoid possible problems, before connecting the valve configure the driver by making the
right changes on the parameters. Select the kind of motor (tEU parameter) and check if the valve is present
in the tEP parameter table reported below:
tEP Model
LSt
(steps*10)
uSt
(steps*10)
CPP
(mA*10)
CHd
(mA*10)
Sr
(step/s)
0 Manual settings Par Par Par Par Par
1 Alco EX4-EX5-EX6 5 75 50 10 500
2 Alco EX7 10 160 75 25 500
3 Alco EX8 500 10 260 80 50 500
4 Danfoss ETS-25/50 7 262 10 10 300
5 Danfoss ETS-100 10 353 10 10 300
6 Danfoss ETS-250/400 11 381 10 10 300
7 Sporlan SEI 0.5-11 0 159 16 5 200
8 Sporlan SER 1.5-20 0 159 12 5 200
9 Sporlan SEI 30 0 319 16 5 200
10 Sporlan SER(I) G,J,K 0 250 12 5 200
11 Sporlan SEI 50 0 638 16 5 200
12 Sporlan SEH(I) 100 0 638 16 5 200
13 Sporlan SEH(I) 175 0 638 16 5 200
Table 6-1 - tEP Parameter Table
CAUTION! The maximum distance between an XEV22 controller and a valve must not exceed 30 feet (10
meters).
Connection
Numbering
ALCO EX*
SPORLAN
SEI-SEH
DANFOSS ETS
4 BLUE WHITE BLACK
2 BROWN BLACK WHITE
3 BLACK RED RED
1 WHITE GREEN GREEN
Table 6-2 - 4-Wire Valves (Bipolar)