Instruction Manual
D100324X012
1061 F & G Actuator
October 2012
15
Figure 5. Locking Mechanism (Size 30, 40, 60, and 68)
MODIFIED
HOUSING
(KEY 20)
PADLOCK
(CUSTOMER
SUPPLIED)
CAP SCREW (4 REQ'D) (KEY 129)
LEVER
34B0458-A
A6808-1
LEVER
CAP SCREW
GROOVE PIN
(KEY 127)
JAM NUT (KEY 128)
MOUNTING PLATE ASSY (KEY 124)
LOWER
LOCKING DISK
MOUNTING
PLATE
(KEY 123)
Installing the Locking Mechanism
Refer to figures 5 and 6 for locking mechanism details and key number locations.
WARNING
Perform the steps in the WARNING at the beginning of the Maintenance section.
1. Refer to instructions in the appropriate valve instruction manual.
2. Disassemble the actuator by following the procedures in the Disassembly section.
For Size 30, 40, 60, & 68 Actuators
1. Attach the mounting plate (key 123) to the modified housing (key 21) as shown in figure 5. Attach it with the cap
screw(key129).Besuretheholeinthecenterofthemountingplatelinesupwiththelargetappedholeinthe
housing.
2. Be sure the jam nut (key 128) is threaded onto the threaded bolt on the mounting plate assembly (key 124) before
threading it into the housing.
3. After the bolt is threaded into the housing, install the groove pin (key 127) into the end of the bolt. (The groove pin
will prevent the threaded bolt from being totally unthreaded from the actuator housing.)