Implementation Basics
Protocol controls the language structure or message format between devices in other words, the rules for
communication. The rules for communication include how master and slave devices initiate communications, as
well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of
the query and response cycles between master and slave devices.
The SiteLink module is configured to act as a slave device on a common network. The common network can be
point-to-point over EIA-232, where one master communicates to one slave device or in a multi-drop configuration
over EIA-485, where multiple slaves reside on a common wire or loop.
Transmission Format
The SiteLink module supports both Modbus RTU (Remote Terminal Unit) and ASCII (American Standard Code for
Information Interchange) transmission modes. The SiteLink module has a choice of transmission medium, baud
rate, character parity and number of stop bits. See chart below.
Physical
Port
Transmission
Mode
Baud Rate Data Bits Parity Bits Stop Bits Default
EIA-232 –
DB9 DCE
RTU 9600 8 None 1 Yes
EIA-232 –
DB9 DCE
ASCII 1200
38.4kbd
(19.2kbd omit)
Configurable Configurable Configurable No
EIA-485 – 2
or 4 wire
RTU or ASCII 1200 –
38.4kbd
(19.2kbd omit)
Configurable Configurable Configurable No