Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Page 118 of 146
Available Points
SiteScan Availability Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Output Watts B 40022 BS22_x
Output Watts C
40023
BS23_x
System Output Va A
System Output Va B
System Output Va C
Alarm Points
Loss Of Communications
40289:00
BA01_x:00
Input Switch Open
40289:01
BA01_x:01
Generator Input Disconnected
40289:02
BA01_x:02
Main AC Neutral Lost
40289:03
BA01_x:03
Load On Battery
40289:04
BA01_x:04
Reserved
40289:05
BA01_x:05
Load On Joint Mode
40289:06
BA01_x:06
Load On Bypass
40289:07
BA01_x:07
No Power Supplied
40289:08
BA01_x:08
Overload Bypass
40289:09
BA01_x:09
Max Xfer Bypass
40289:10
BA01_x:10
False Operation
40289:11
BA01_x:11
UPS Overload
40289:12
BA01_x:12
Battery Shutdown Imminent
40289:13
BA01_x:13
Inverter Not Sync
40289:14
BA01_x:14
DC Under Voltage Shutdown
40289:15
BA01_x:15
Inverter Fault
40290:00
BA02_x:00
Inverter DC Offset Overrun
40290:01
BA02_x:01
Inverter Contactor Fail
40290:02
BA02_x:02
Inverter Over Current
40290:03
BA02_x:03
Inverter Communication Fail
40290:04
BA02_x:04
Rectifier Input Fuse Blown
40290:05
BA02_x:05
Rectifier Startup Fail
40290:06
BA02_x:06
Rectifier Fault
40290:07
BA02_x:07
Rectifier Over Current
40290:08
BA02_x:08
Rectifier Communication Fail
40290:09
BA02_x:09
Control Power Fail
40290:10 BA02_x:10
Fan Fail
40290:11
BA02_x:11
Battery Overtemperature
40290:12
BA02_x:12
Ambient Overtemperature
40290:13
BA02_x:13
Rectifier Overtemperature
40290:14
BA02_x:14
Rectifier Inductor Overtemp
40290:15
BA02_x:15