of the two regulators. The decision to use either an
upstream or downstream monitoring system is largely
a matter of personal preference or company policy.
In normal operation of a wide open conguration,
the working regulator controls the system’s outlet
pressure. With a higher outlet pressure setting, the
monitor regulator senses a pressure lower than its
setpoint and tries to increase outlet pressure by going
wide open. If the working regulator fails, the monitoring
regulator assumes control and holds the outlet
pressure at its outlet pressure setting.
Figure 5 shows an upstream wide-open monitor
EZH Series (failed-close) and a downstream active
regulator EZHSO Series (failed-open). In this
installation, if the EZHSO Series regulator no longer
controls downstream pressure, it will remain open,
letting the EZH Series monitor regulator take control
of the downstream pressure. If the EZH Series should
fail, the monitor regulator will go closed and protect
against overpressure to the downstream system.
Figure 5. Wide-Open Monitoring System Operational Schematics
M1164
EZH SERIES
EZHSO SERIES
TYPE
SA/2
CHECK VALVE
CHECK VALVE
TYPE
SA/2
TYPE
PRX
TYPE
PRX
M
V
R
R
S
L A
B
V
M
S
L
A
B
Working Monitoring System (Figure 6)
In a working monitoring system, the upstream
regulator requires two pilots and it is always the
monitoring regulator. The additional pilot permits
the monitoring regulator to act as a series regulator
to control an intermediate pressure during normal
operation. In this way, both units are always operating
and can be easily checked for proper operation. See
Installation section.
In normal operation, the working regulator controls
the outlet pressure of the system. The monitoring
regulator’s working pilot controls the intermediate
pressure and the monitoring pilot senses the system’s
outlet pressure. If the working regulator fails, the
monitoring pilot will sense the increase in outlet
pressure and take control.
TYPE PRX
S - BLEED PORT
B - SUPPLY PORT
L - LOADING PORT
A - SENSING PORT
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
PILOT SUPPLY PRESSURE
LOADING PRESSURE
TYPE SA/2:
V - SENSING PORT
R - PILOT SUPPLY PORT
M - INLET PORT