Emerson 644 Especificaciones Pagina 129

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 182
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 128
119
Reference Manual
00809-0200-4728, Rev RA
Appendix A: Specifications and Reference Data
April 2015
Specifications and Reference Data
A.5 Specifications and reference data for 644 HART
Head Mount
(Device Revision 7 or previous)
A.5.1 Functional specifications
Inputs
User-selectable; sensor terminals rated to 42.4 Vdc. See “Accuracy on page 98 for sensor
options.
Output
Single 2-wire device with either 4-20 mA/HART, linear with temperature or input. Device
supports protocol revision HART 5.
Isolation
Input/output isolation tested to 600 Vrms.
Local display
The optional five-digit integral LCD display includes a floating or fixed decimal point. It can also
display engineering units (°F, °C, °R, K, W, and mV), mA, and percent of span. The display can be
configured to alternate between selected display options. Display settings are preconfigured at
the factory according to the standard transmitter configuration. They can be reconfigured in
the field using a compliant Field Communicator.
Humidity limits
0–95% relative humidity
Update time
0.5 sec. single sensor mode
1.0 sec. dual sensor mode
Accuracy
(default configuration) PT 100
HART (0-100 °C): ±0.18 °C
Vista de pagina 128
1 2 ... 124 125 126 127 128 129 130 131 132 133 134 ... 181 182

Comentarios a estos manuales

Sin comentarios