Y690A Series
6
in Figures 5, 6, and 7.
1. Remove the cap screws (key 2, Figure 7) and
separate the diaphragm casing (key 4) from the
body (key 1).
2. Remove and inspect the body seal O-ring (key 11)
and the backup ring (key 50). See Figure 4.
3. Inspect and replace the orice (key 5) if necessary.
Protect the orice seating surface during
disassembly and assembly. Lubricate the threads
of the replacement orice with a good grade of light
grease and install with 29 to 37 foot-pounds (39 to
50 N•m) of torque.
4. Remove the cotter pin (key 15) to replace the
disk assembly (key 13) or to inspect the throat
seal O-ring (key 31, Figure 6) on the
Types Y690AM and Y690AHM.
5. To replace the pitot tube (key 32, Figure 5) on
the Types Y690A and Y690AH, remove the pitot
tube screws (key 33), install the new pitot tube,
and secure with the pitot tube screws (key 33).
Position the pitot tube so that it points into the
outlet of the body by rotating the guide insert
(key 18).
6. To inspect the throat seal O-ring (key 31, Figure 6)
on the Types Y690AM and Y690AHM, remove the
machine screw (key 33, Figure 6). Replace if
necessary, and reassemble.
7. Install the disk assembly (key 13) and secure it
with the cotter pin (key 15).
8. Place back-up ring (key 50) into the body (key 1).
Then place the body seal O-ring (key 11) into the
body. See Figure 4.
9. Place the diaphragm casing (key 4) on the body
(key 1). Secure the diaphragm casing to the body
with the cap screws (key 2, Figure 7).
Diaphragm and Spring Case Area
This procedure is for gaining access to the spring,
diaphragm, lever assembly, and stem. All pressure
must be released from the diaphragm casing before
these steps can be performed.
To Change the Control Spring:
Note
Any remote control drive unit used
with a Y690A Series regulator must be
removed from the spring case (key 3)
before these steps can be performed.
1. Remove the closing cap (key 22), and turn the
adjusting screw (key 35) counterclockwise to
remove all the compression from the control
spring (key 6).
2. Change the control spring (key 6) to match the
desired spring range.
3. Replace the adjusting screw (key 35).
4. Install a replacement closing cap gasket (key 25),
if necessary, and reinstall the closing cap (key 22).
5. If the spring range was changed, be sure to
change the stamped spring range on the nameplate.
To Disassemble and Reassemble
Diaphragm Parts:
Key numbers are referenced in Figures 5, 6, and 7.
1. Remove the closing cap (key 22), and turn the
adjusting screw (key 35) counterclockwise to
remove the adjusting screw and the control
spring (key 6).
2. Remove the spring case hex nuts (key 23, not
shown), cap screws (key 24), and spring case
assembly (key 3).
3. Remove the diaphragm (key 10) plus attached parts
by tilting them so that the pusher post (key 8) slips
off the lever assembly (key 16). To separate the
diaphragm (key 10) from the attached parts, unscrew
the spring holder screw (key 38) from the pusher
post (key 8).
4. Inspect the pusher post (key 8) and the post seal
O-ring (key 48), replace if required.
5. Remove hex nut (key 21) to separate the
diaphragm (key 10) and attached parts.
6. To replace the lever assembly (key 16), remove
the machine screws (key 17). To replace the
BODY SEAL
O-RING (KEY 11)
BACKUP RING (KEY 50)
BODY (KEY 1)
Figure 4. Expanded View of the Body Area
Showing the O-ring and Backup Ring Placement
Comentarios a estos manuales