Type HSR
6
Type HSR regulators provide internal relief that limits the
total outlet pressure build-up over setpoint. This internal relief
may be adequate for the application, if not, provide additional
pressure relief or a pressure-limiting device downstream.
Regulators should be inspected for damage after any
overpressure condition.
Startup
WARNING
!
To avoid personal injury or property damage
due to explosion or damage to regulator or
downstream components during startup,
release downstream pressure to prevent an
overpressure condition on the diaphragm of
the regulator.
In order to avoid an overpressure condition
and possible equipment damage, pressure
gauges should always be used to monitor
pressures during startup.
1. Check to see that all appliances are turned off.
2. Slowly open the upstream shutoff valve.
3. Slowly open the downstream shutoff valve.
4. Check all connections for leaks.
5. Make nal control spring adjustments according to the
adjustment procedures.
6. Light the appliance pilots.
Adjustment
To increase the outlet pressure setting of the regulator,
the adjusting screw (key 26, Figure 6) must be turned
clockwise. This requires removal of the closing cap (key 8).
To reduce the outlet pressure setting, turn the adjusting
screw counterclockwise. A pressure gauge should always be
used to monitor downstream pressure while adjustments are
being made. Do not adjust the spring to produce an outlet
pressure setting above the limit identied on the information
label. If the required pressure setting is not within the range
of the spring being used, substitute with the correct spring,
see Table 2. When changing the spring, also change the
range identied on the information label to indicate the
actual pressure range of the spring in use. After the spring
adjustment has been completed, replace the closing cap.
Shutdown
WARNING
!
To avoid personal injury or property
damage due to explosion or damage to
regulator or downstream components
during shutdown, release downstream
pressure to prevent an overpressure
condition on the regulator diaphragm.
Installation arrangements may vary, but in any installation it is
important that the valves be opened or closed slowly. These
steps apply to the typical installation.
1. Slowly close the downstream shutoff valve.
2. Slowly close the upstream shutoff valve.
3. Open vent valves downstream of the regulator.
4. Open vent valves upstream of the regulator.
Maintenance
WARNING
!
Avoid personal injury or damage to
property from sudden release of pressure
or uncontrolled gas or other process uid.
Before starting to disassemble, isolate the
regulator from all pressure and cautiously
release trapped pressure from the regulator.
Use gauges to monitor inlet, loading and outlet
pressures while releasing these pressures.
These procedures are for gaining access to the diaphragm,
valve disk and orice. All pressure must be released from the
diaphragm actuator assembly before the following steps can
be performed.
While using the following procedures, refer to Figure 6 for
key number locations.
Diaphragm Replacement
1. Remove the closing cap (key 8) and adjusting screw
(key 26).
2. Remove the spring case machine screws (key 9) out of
the spring case (key 1) and remove the spring case and
control spring (key 25).
3. Lift the diaphragm (key 11) slightly and slide it away
from the lever (key 4), so that the pusher post (key 12)
releases the lever.