1.3.7 Mounting:
(A) The shelf is designed for mounting in a 19-inch or 23-inch wide relay rack with 1-3/4 inch
multiple drilling.
(B) This product is intended only for installation in a Restricted Access Location on or above a
non-combustible surface.
(C) This product must be located in a Controlled Environment with access to Craftspersons
only.
(D) This product is intended for installation in Network Telecommunication Facilities (CO, vault,
hut, or other environmentally controlled electronic equipment enclosure).
(E) This product is intended to be connected to the common bonding network in a Network
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic
equipment enclosure).
(F) Typical industry standards recommend minimum aisle space clearance of 2'6" for the front
of the relay rack and 2' for the rear of the relay rack.
1.4 System Compliance Information
1.4.1 Safety Compliance: This unit meets the requirements of UL 60950, Standard for Information
Technology Equipment, and is UL Recognized as a power supply for use in Telephone,
Electronic Data Processing or Information Processing Equipment. This unit meets the
requirements of CAN/CSA 22.2, No. 60950-00 and is tested and Certified by UL ("c UR") as a
Component Type Power Supply.
1.4.2 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory
(NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS
compliance reports.
Converter Modules: In order to remain compliant during a fan failure condition, the system
must operate with a redundant module installed.
1.5 System Standard Features
1.5.1 Local Indicators: The following local indicators are provided on the front of the main shelf’s
front door.
(A) Circuit Breaker or Fuse Open (Red LED)
(B) Input Voltage OK (Green LED)
(C) Converter Major (Red LED)
(D) Converter Minor (Yellow LED)
1.5.2 Test Points: The following test points are provided on the front of the main shelf’s front door.
(A) Output Voltage: Provided for measuring system output voltage.
(B) Output Current: Provided for measuring system output current. Scale is User selectable
for 400A/50mV or 1A/1mV. Current measurement is User selectable to be referenced to
plus battery, minus battery, or no reference.
1.5.3 Emergency Shutdown Input (ESTOP): The converter modules can be inhibited by applying
an external ground signal (24V Return). Converter modules automatically restart upon removal
of the ground signal.
1.5.4 External Alarm Circuits: A set of Form-C relay contacts, rated for 1 ampere at 30 volts DC or
0.3 ampere at 110VDC, is provided for each of the following alarms. Relays are energized for
normal operating conditions and de-energized for an alarm condition.