Toggle-Handle Bullet Nose Type Circuit Breakers
for Use in Lists 115 and 125
Ampere
Rating
Number of Poles
(and mounting
positions
required)
P/N
Lugs
Electrical
Trip
1
(White
Handle)
Electrical/
Mechanical
Trip
2
(Black Handle)
Up to 2 AWG lead sizes, use
lugs in Table 7 (1/4” clearance
holes on 5/8” centers.
From 1/0 to 350 kcmil lead
sizes, use lugs in Table 7
(Special Crimp Lug).
100 1 102286 101610
125 2 516991 516838
Use lugs in Table 7
(Special Crimp Lug).
150
2 516993 516839
175
(see
below)
2 144883 144884
200
(see Caution below)
2 121831 121832
225
(see
below)
3 144885 144886
Use lugs in Table 7 (Special
Crimp Lug) plus special lug
adapter P/N 545346 or lug
adapters listed in Table 7.
3 121835 121836
See Table 8 for recommended load distribution wire sizes.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an
empty mounting position between it and any other overcurrent protective device.
Table 5
Toggle-Handle Bullet Nose Type Circuit Breakers
for Use in Lists 115 and 125