Distribution Devices
GMT Load Distribution Fuses
Features
♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8)
0-10A GMT load distribution fuses.
♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses.
♦ Each List BG and NG Distribution Unit holds up to ten (10) 0-15A GMT load distribution fuses.
♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere
fuses, for which load should not exceed 70% of device rating.
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (GMT Fuses) (Lists BG and NG only), Load Distribution Wiring (GMT
Fuses) (Lists BF, LF, and NF only), and Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA,
and NA) under WIRING NOTES for additional wiring restrictions.
Ordering Notes
1) Order GMT fuses per Table 2.
Replacement
248872600 ---
Replacement Safety
Fuse Cover
BC, LC, NC,
102774
--
Table 2
GMT Fuses