Emerson FIELDVUEDVC6200p Manual de instrucciones Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 10
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
Instruction Manual Supplement
D104019X012
DVC6200p
November 2014
2
The example below shows an AO Module, number 5, assigned to Slot 1. The slots that are not used have been assigned
as an EMPTY_MODULE. Different Class 1 Masters will present different views and may have a different number of
configurable slot locations.
The below example is from a Siemens PCS7. On the right pane the DVC6200p is selected. All of the modules available
for the device are listed. In this example Module 9 has been selected.
With the graphic image of the DVC6200p highlighted slot assignments are made in the table for the DVC6200p.
The AO module 9 has been assigned to Slot 0 (the first slot) in this example. Unused slots must be defined as
EMPTY_MODULE as shown below and not as Blank or Null. Most control systems define the Inputs (I) and Output (Q)
address ranges automatically.