CS200 Series
2
Table 2. Inlet Pressure Ratings and Flow and Sizing Coefcients
Table 1. Available Congurations
TYPE
ORIFICE SIZE
MAXIMUM
OPERATING INLET
PRESSURE TO
PROVIDE OPTIMUM
PERFORMANCE
(1)(2)
MAXIMUM
EMERGENCY INLET
PRESSURE
(2)
FLOW
COEFFICIENTS
(WIDE-OPEN)
C
1
IEC SIZING COEFFICIENTS
Inch mm psig bar psig bar C
g
C
v
X
T
F
D
F
L
CS200
1/8 3.2 125 8.6
175 12.1
12 0.4 30 0.53 0.87
0.89
3/16 4.8 125 8.6 24 0.8 30 0.58 0.82
1/4 6.4 125 8.6 44 1.52 29 0.53 0.85
3/8 9.5 60 4.1 102 3.3 31 0.6 0.83
1/2 13 40 2.8 172 4.4 39 0.97 0.72
CS205
and
CS206
1/8 3.2 125 8.6 17 0.6 28 0.5 0.82
3/16 4.8 125 8.6 37 1.4 27 0.49 0.8
1/4 6.4 125 8.6 65 2.2 30 0.5 0.8
5/16 7.9 100 6.9 88 2.7 33 0.65 0.79
1. Inlet pressures based on lockup performance. For maximum inlet pressure values with optimum regulating performance, refer to the applicable Flow Capacity Table on CS200 Series Bulletin.
2. To comply with ANSI B109.4 relief requirements, the maximum inlet pressure may need to be reduced.
Description
The CS200 Series regulators are typically installed
on industrial and commercial applications. All
constructions include internal pressure registration.
Types CS200IR, CS205IR, and CS206IR contain an
internal relief valve. Types CS200IN and CS205IN do
not contain internal relief.
!
WARNING
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion
and/or re causing property damage and
personal injury or death.
Fisher
®
regulators must be installed,
operated, and maintained in accordance
with federal, state, and local codes,
rules and regulations, and Emerson
Process Management Regulator
Technologies, Inc. (Regulator
Technologies) instructions.
If the regulator vents gas or a leak
develops in the system, service to
the unit may be required. Failure
to correct trouble could result in a
hazardous condition.
Call a gas service person to service the
unit. Only a qualied person shall install
or service the regulator.
TYPE NUMBER OPTIONS
C S 2 0
OVERPRESSURE PROTECTION MODULE
0 Without Overpressure Protection Module
5 With Secondary Seat™ Protection
6
With Secondary Seat Protection with bleed to indicate Secondary Seat
is functioning
PRESSURE REGISTRATION
I Internal Registration
RELIEF
N Non-Relief
R Internal Relief