Liebert® APS™ MBCUser Manual – Rack-Mount Maintenance Bypass Cabinet
General DescriptionLiebert® APS™ MBC 61.4 Operating ModeThe Liebert APS MBC permits maintaining power to all connected equipment during maintenance of
Installation7Liebert® APS™ MBC2.0 INSTALLATIONThis chapter provides the steps and procedures for installing the Liebert APS MBC, including preparation
InstallationLiebert® APS™ MBC 8Figure 6 Installing the cage nuts3. Using the hook on the rear flange of the rack-mount rail, clip it onto the rear ver
Installation9Liebert® APS™ MBCFigure 8 Securing the front of the rack-mount rails5. Remove the Liebert APS MBC from the shipping carton and install it
InstallationLiebert® APS™ MBC 10Figure 10 Completed view of the Liebert APS MBC installation8. Refer to 2.4 - Cable Selection And Connection for wirin
Installation11 Liebert® APS™ MBC2.4.1 Cable SelectionSelect proper cable size/amperage based on the Liebert APS MBC model. The models have different c
InstallationLiebert® APS™ MBC 122.4.2 Cable Connection For Liebert APS UPS 200-240V input/outputRefer to Figures 12 and 13 for the cable connections w
Installation13 Liebert® APS™ MBCFigure 15 Connection of Liebert APS MBC’s lower terminal block (from main AC source/to main distribution panel)2.4.3 C
InstallationLiebert® APS™ MBC 14Figure 17 Connection of Liebert APS MBC’s lower terminal block (from main AC source / to main distribution panel)Table
Installation15 Liebert® APS™ MBC2.4.4 Cable Connection for Liebert APS UPS 200/100-240/120V Input/OutputRefer to Figures 18 and 19 for the cable conne
CONTACTING EMERSON NETWORK POWER FOR SUPPORTTo contact Emerson Network Power Liebert Services for information or repair service in the United States,
OperationLiebert® APS™ MBC 163.0 OPERATIONThis chapter gives a detailed description on the Liebert APS MBC operation, including startup, shutdown and
Operation17 Liebert® APS™ MBC3.4 Transfer of the System from Maintenance Bypass to UPSTo transfer to UPS from maintenance bypass:1. Close the UPS inpu
TroubleshootingLiebert® APS™ MBC 184.0 TROUBLESHOOTINGTable 5 TroubleshootingProblem Cause SolutionBypass Indicator (amber) not illuminatedBypass not
Specifications19 Liebert® APS™ MBC5.0 SPECIFICATIONSTable 6 SpecificationsItem SpecificationGeneralUnit RatingASMBCR2 Series: 125A maxASMBCR1 Series:
POD—OptionalLiebert® APS™ MBC 206.0 POD—OPTIONAL6.1 IntroductionPower Output Distribution (PODs) are optional, integral distribution units that may be
POD—Optional21 Liebert® APS™ MBC6.2 Installing the PODTo connect the POD:1. Unscrew the two screws of the cover of the POD port and remove the cover,
POD—OptionalLiebert® APS™ MBC 22
While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumes noresponsibility and disc
iTABLE OF CONTENTSCONTACTING EMERSON NETWORK POWER FOR SUPPORT . . . . . . . . . . . . . . . INSIDE FRONT COVERIMPORTANT SAFETY PRECAUTIONS . . . .
iiFIGURESFigure 1 General Liebert APS MBC appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4F
Important Safety Precautions1Liebert® APS™ MBCIMPORTANT SAFETY PRECAUTIONSSAVE THESE INSTRUCTIONSThis manual contains important safety instructions. R
Important Safety PrecautionsLiebert® APS™ MBC 2The Liebert APS MBC complies with the requirements of EMC Directive 2004/108/EC and the published techn
Glossary Of Symbols3Liebert® APS™ MBCGLOSSARY OF SYMBOLSRisk of electrical shockIndicates caution followed by important instructionsAC inputAC outputC
General DescriptionLiebert® APS™ MBC 41.0 GENERAL DESCRIPTIONRead this manual thoroughly to ensure proper installation and operation of this unit.Inst
General Description5Liebert® APS™ MBC1.2.1 Bypass Indicator LEDThe amber Bypass Indicator illuminates when the maintenance bypass source is available.