NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
•
Select the type of LVD Contactor. This setting
should not be changed.
SMDU 1 LVD MENU
Main Menu / Settings / LVD / SMDU 1 LVD
Note: For WEB Interface; menu items are found under Device
Information / LVD Group / SMDU 1 LVD / Settings Tab.
"SMDU 1 LVD" Parameter Settings:
•
Enables or disables LVD1.
•
Sets LVD1 to disconnect on a voltage or
time setpoint.
•
LVD1 low voltage disconnect setting
(when LVD set for voltage).
•
LVD1 reconnect setting (when
LVD set for voltage).
•
Delay time period until LVD1
reconnects once voltage recovers (when LVD set for
voltage).
•
The time period before LVD1
disconnection once an AC fail condition occurs
(when LVD set for time).
•
Select if LVD1 can disconnect
only if LVD2 has disconnected, or none.
•
Enables or disables LVD2.
•
Sets LVD2 to disconnect on a voltage or
time setpoint.
•
LVD2 low voltage disconnect setting
(when LVD set for voltage).
•
LVD2 reconnect setting (when
LVD set for voltage).
•
Delay time period until LVD2
reconnects once voltage recovers (when LVD set for
voltage).
•
The time period before LVD2
disconnection once an AC fail condition occurs
(when LVD set for time).
•
Select if LVD2 can disconnect
only if LVD1 has disconnected, or none.
•
Enables or disables the High Temperature 1
Disconnect feature. This feature causes LVD1 contactors
to open (disconnect) if a high temperature event occurs.
(See HTD selections in the "LVD Group" Parameter
Settings.)
•
Enables or disables the High Temperature 2
Disconnect feature. This feature causes LVD2 contactors
to open (disconnect) if a high temperature event occurs.
(See HTD selections in the "LVD Group" Parameter
Settings.)
AC
RECT AC MENU
Main Menu / Settings / AC / Rect AC
Note: For WEB Interface; menu items are found under Device
Information / AC Group / Rect AC / Settings Tab.
"Rect AC" Parameter Settings:
•
Enter the nominal line-to-neutral
voltage (single phase rectifier) or nominal line-to-line
voltage (three phase rectifier).
•
Sets the Mains Fail Alarm 1 value
(percent of nominal).
•
Sets the Mains Fail Alarm 2 value
(percent of nominal).
• Phase A Voltage Low 1 (Nominal Minus "Mains Fail Alarm
1 Percent of Nominal)
• Phase A Voltage Low 2 (Nominal Minus " Mains Fail Alarm
2 Percent of Nominal)
• Phase A Voltage High 1 (Nominal Plus " Mains Fail Alarm 1
Percent of Nominal)
• Phase A Voltage High 2 (Nominal Plus "V Mains Fail Alarm
2 Percent of Nominal)
Phase A used in the example above, Phase B and Phase C are
similar.
EIB
EIB 1 MENU
Main Menu / Settings / EIB / EIB 1
Note: For WEB Interface; menu items are found under Device
Information / EIB Group / EIB 1 / Settings Tab.
"EIB 1" Parameter Settings:
•
Shunt # Set As (Not Used, General, Load, Battery):
a.
Indicates this shunt input is not used.
b.
Indicates the measurement of the shunt
will be displayed and will not be added to Total DC
Load or Total Battery Load.
c.
Indicates the measurement of the shunt will
be displayed and added to the Total DC Load.