Installation Guide Section 5957
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AM, March 26, 2014
Page 53
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installing Load Lug Adapter Plates
into Distribution Only Bays (continuation)
4-Position
Lug Adapter Kit
P/N 534420
Busbars
P/O Dist.
Bay
Customer
Supplied
Lugs
Customer
Supplied
Lugs
(4) 3/8-16 x 1-1/2" Bolt,
P/N 227647000
(4) 3/8" Belleville Lock Washer,
P/N 214825000
Torque to 180 in-lbs.
(1) Adapter Busbar,
P/N 534421
(1) Spacer Busbar,
P/N 528806
(1) Adapter Busbar,
P/N 534421
(8) 3/8-16 Hex Nut,
P/N 228567100
(8) 3/8" Flat Washer,
P/N 214204100
(4) 3/8-16 x 2" Bolt,
P/N 227647400
(4) 3/8" Belleville Lock Washer,
P/N 214825000
Note: Apply Electrical Anti-Oxidation
Compound to all Busbar
Mating Surfaces.
Note: Concave Side of Belleville Washer Faces Busbar,
Convex Side Faces Bolt or Nut.