Networking
149
1-800-893-2321
149
CTNet Fieldbus
The CTNet fieldbus is a 5 Mbit token ring network
that supports peer-to-peer communications. Utilizing
the field-proven ANSI/ATA 878.1 ARCNET standard as
a foundation, CTNet includes a custom protocol stack
that supports cyclic data and one shot transactions.
The CTNet fieldbus employs an RS485 transformer-
isolated physical layer to allow usage of a convenient
and inexpensive two-wire shielded, non-phasic cable.
Two methods of data exchange are supported: cyclic
data and non-cyclic data. Cyclic data exchanges are
pre-programmed block transfers (20 registers max.)
between coprocessors at either a fast or slow rate. Non-
cyclic exchanges are asynchronous transfers initiated by
application programs or SCADA / HMI devices.
X-Link Network Bridge (2510-00010)
For those applications
requiring connection of
CTNet systems with third-
party networks and PLCs,
the X-Link Bridge provides
a solution. The X-Link
engine accepts a CTNet
ISA card and a third-party
network card, such as A-B Data Highway. Special
driver software allows communication between the
two networks. Users may map registers on a PLC
to parameters in a CTNet-equipped drive and once
specified, the exchanges run continuously using the X-
Link box as the mediator. The X-Link currently supports
over 50 industrial networks and is the only system
available that can connect to an A-B Data Highway.
Repeaters
For extending CTNet cable segments
and creating star topologies, there are
three types of repeaters available:
CTNet Cable
Control Techniques
supplies a high quality
shielded twisted-pair cable
suitable for high-speed data
transmission. It is available
in three standard lengths or
any specified non-standard
length.
100 Meters CTNet-100
200 Meters CTNet-200
Non-standard (bulk in feet) CTNet-xxx*
* xxx= number of feet
Beckhoff Remote I/O
The high-quality Beckhoff
I/O system is available for
CTNet systems. Beckhoff
systems for CTNet include
a SSP7200-Rev C bus coupler
and a large variety of snap-on
terminal blocks allowing up
to 256 digital inputs or outputs and up to 100 analog
inputs and outputs per bus coupler. Up to 64 Beckhoff
I/O systems can be attached to a CTNet network. I/O
points exist as CTNet parameters and can be easily read
or written. Cyclic data transfers are also supported for
efficient I/O sampling.
Contact Control Techniques for details on the wide
range of available Beckhoff Remote I/O options.
CTIU200 Operator Interface Unit
Control Techniques
supports several HMI
displays, and of these the
CTIU200 model, with the
CTIU200-CTNet-Rev C option,
supports CTNet operations.
The CTIU200 is a high-end
operator interface unit featuring a 16-line,
40-character display, 37 keys, 300 pages of user-
programmable displays, a scripting language, graphical
charts and trends, recipe support and user-friendly
modification of parameter values. A sophisticated
Windows programming tool creates the custom
application and downloads it into the CTIU200
for operation.
Cable Length Catalog Number
Two-output (3-port) Repeater (Hub) CTNet-Hub-Rev D
Twisted-pair to Fiber Optic Repeater CTNet FIB-Rev D
Hybrid Hub for connecting
previous versions of CTNet CTNet Hybrid Hub
hardware to current versions
Description Catalog Number