Emerson ATEX Guía de instalación Pagina 3

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 22
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 2
Quick Installation Guide
00825-0100-4825, Rev DB
February 2011
Rosemount 248
3
STEP 1: CONFIGURE (BENCH CALIBRATION)
The Rosemount 248 communicates using the 375 Field Communicator (communication
requires a loop resistance between 250 and 1100 ohms. Do not operate when power is
below 12Vdc at the transmitter terminal). Refer to the Rosemount 248 Reference Manual
(document number 00809-0100-4825) and the 375 Field Communicator Reference Manual
(http://www.fieldcommunicator.com/suppmanu.htm) for more information.
Connecting a Field Communicator
The Hand-held Communicator Field Device Revision Dev v1, DD v1 is required for complete
functionality.
Figure 1. Connecting a Communicator to a Bench Loop
Verify Transmitter Configuration
To verify operation using a Field Communicator, refer to the Fast Keys below. Refer to the
Rosemount 248 Reference Manual (document number 00809-0100-4825) for more detailed
description.
Function Fast Keys Function Fast Key
Active Calibrator 1, 2, 2, 1, 3 Poll Address 1, 3, 3, 3, 1
Alarm/Saturation 1, 3, 3, 2 Process Temperature 1, 1
AO Alarm Type 1, 3, 3, 2, 1 Process Variables 1, 1
Burst Mode 1, 3, 3, 3, 3 PV Damping 1, 3, 3, 1, 3
Burst Option 1, 3, 3, 3, 4 PV Unit 1, 3, 3, 1, 4
Calibration 1, 2, 2 Range Values 1, 3, 3, 1
Configuration 1, 3 Review 1, 4
D/A Trim 1, 2, 2, 2 Scaled D/A Trim 1, 2, 2, 3
Damping Values 1, 1, 10 Sensor Connection 1, 3, 2, 1, 1
250 R
L
1100
Power Supply
Field Communicator
Rosemount 248 Transmitter
00825-0100-4825.fm Page 3 Friday, February 18, 2011 11:49 AM