Ordering Code Valve Connections and Configuration • 3
4 Valve Connections and Configuration
If you can locate your valve in the table, select the valve through the tEP parameter. This way, you can be
sure of the correct configuration (refer to Table 4-1).
Regarding connections, use Table 4-2 below for a quick reference on the connection mode for valves of dif-
ferent manufacturers. In any case, the unique and valid reference has to be considered the datasheet made by
manufacturer of the valve:
CAUTION! To avoid possible problems, before connecting the valve configure the driver by making the right
changes on the parameters. Select the kind of motor (tEU parameter) and check if the valve is present in the
tEP parameter table reported below:
tEP Model
LSt
(steps*10)
uSt
(steps*10)
CPP
(mA*10)
CHd
(mA*10)
Sr
(step/s)
0 Manual settings Par Par Par Par Par
1 Sporlan SEI 0.5-20 10 159 20 5 200
2 Sporlan SEI 30 20 319 20 5 200
3 Sporlan SEH 50-250 40 638 20 5 200
4Alco EX5-EX6 10754010450
5 Alco EX7 25 160 75 25 330
6 Alco EX8 330 step/s 25 260 80 50 330
7 Alco EX8 500 step/s 25 260 80 50 500
8 Danfoss ETS-25/50 20 262 14 8 120
9 Danfoss ETS-100 30 353 14 8 120
10 Danfoss ETS-250/400 35 381 14 8 120
Table 4-1 - tEP Parameter Table
Connection
Numbering
ALCO EX* ALCO EX 5/6
SPORLAN
SEI-SHE
DANFOSS ETS
4WHITEBLUEWHITEBLACK
2 YELLOW BROWN BLACK WHITE
3 BROWN BLACK RED RED
1 GREEN WHITE GREEN GREEN
Table 4-2 - 4-Wire Valves (Bipolar)