2.9.2 Wiring
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24 AWG
or larger wire, and do not exceed 5000 feet (1500 meters).
Figure 2-16. 4-20 mA HART wiring
Do not connect the power signal wiring to the test terminals. Voltage may burn out the
reverse-polarity protection diode in the test connection.
R
L
250
Power
Supply