10MRLDS I&O Manual 026-1307 Rev 4 28-JUN-2011
5.2.6 Modbus Output
See Table 5-3 below for Modbus registers in the
MRLDS Unit. Baud rate: 19,200; each byte is 8 (eight)
bits with no parity and 2 (two) stop bits.
5.3 MRLDS Gateway
5.3.1 MRLDS Gateway Setup on
I/O Network
Modbus versions of the MRLDS must be connected to
the 810-3040 MRLDS Gateway. The MRLDS Gateway
can be mapped in either of two ways: it can be set up on
I/O Net as an IRLDS application or as a 16AI board.
Select by setting the Gateway’s dip switch #5 to the OFF
or ON position (Figure 5-6).
Figure 5-5
- MRLDS Termination (Inside Lower Left of Cover)
Register
Name
PDU
Address
Logical
Address
Range
Fault and
Module
State
0x0000 1 Under Range
2 (msb)
Under Volt-
age 8 (msb)
Temperature
10 (msb)
Lamp Fail
40 (msb)
Test Mode
80 (msb)
Warm Up
Complete
0 (Lsb)
Cal/Setup
2 (Lsb)
Table 5-3
- RS485 Output Specifications
J6
J5J4 J3
J2 J1
Termination
jumper
J6
J1
Factory
Mode
4 (Lsb)
Trouble
Mode
8 (Lsb)
Gas
Number
0x0001 2 0 to 40
Gas Con-
centration
0x0002 3 -20 to 1050
(PPM)
Gas
Numbers
R-22 = 6
R-404A = 27
R-134a = 15
Figure 5-6
- I/O Network Modes
Table 5-3 - RS485 Output Specifications
SELECT I/O NET MODE
OFF = IRLDS
ON = 16AI
ON = 16AIOFF = IRLDS
ON