Basis Weight Actuator
13
Figure 9. Transformer Schematic
E0014 / IL
JUMPER
over-tightened, the switch action may
not allow the switch to close after it has
been tripped.
4. Turn on power to the Stepmotor Interface.
5. Check to be sure the valve rotation indicator in the
Stepmotor Interface and in the optional remote station
show zero percent for 0 degrees of valve rotation (fully
closed) and 100 percent for 90 degrees of valve rota-
tion (fully open). Refer to the Adjustment section for
adjustment instructions.
6. Adjust the stroking speed with the adjustments on
the IC500 card faceplate (key 3, figure 4). Clockwise
rotation of the adjustment increases the speed. If the
speed increases too much, the the torque will drop off
and cause the motor to stall.
With no pressure applied to the valve, apply a signal to
operate the valve in both directions (opening and clos-
ing) and in both the manual (MAN) and computer
(COMP) operating modes. As the valve ball or disk is
rotating, adjust speed until the motor operates smooth-
ly and as quietly as possible. If the valve moves with a
jerky motion, continue to adjust the speed. Refer to the
Stroking Speed section for more information.
After the valve is in service, you can adjust the speed
again. If it appears that motor torque is too low, de-
crease stroking speed.